9907-147 ProTech 203 De-Energize-to-Trip Overspeed
This de-energize-to-trip system has a 100 Hz to 32 kHz speed-sensing frequency range and a ±(0.05% x Trip
Point in Hz +2 Hz) accuracy rating. Overspeed detection functions are carried out by three individual speed-sensing
units, which act independently to monitor speed and perform speed calculations. The three units are in a
two-out-of-three vote configuration, so a prime mover trip relay will only occur if overspeed conditions are detected by at least two of the units.
The trip-point frequency range of ProTech overspeed protection model 9907-147 is 250 Hz to 25 kHz. Trip
set points are programmed for each of the units separately (they must be programmed identically for accurate
outputs) using the operator interfaces. There is one interface per speed-sensing unit. Each one has:
- Two-line by 16-character LCD display
- Touchpad
- Potentiometer
- LED indicators
- Alarm output
Programming and testing functions are locked to prevent unauthorized changes. One key switch to move between
MONITOR mode and PROGRAM mode is connected to all three units.