MTL1173  potentiometer input converter

The MTLx511 enables a safe-area load to be controlled by a switch or
proximity detector located in a hazardous-area. When selected, open
or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for the channel is selected by a switch on the side of the
module and output is provided by changeover relay contacts.

Category:

Description

MTL1173  potentiometer input converter

The MTLx511 enables a safe-area load to be controlled by a switch or
proximity detector located in a hazardous-area. When selected, open
or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for the channel is selected by a switch on the side of the
module and output is provided by changeover relay contacts.

MTL5553

Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if an
input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “MTL1173  potentiometer input converter”

Your email address will not be published. Required fields are marked *

Post comment