Description
1900/65A-00-01-03-01-01 1900/65A General Purpose Equipment Monitor
Product description
The 1900/65A General Purpose Equipment Monitor isdesigned to continuously monitor and protect equipmentthat is used in a variety of applications and industries. Themonitor’s low cost makes it an ideal solution for general-purpose machines and processes that can benefit fromcontinuous monitoring and protection.
inputs
The 1900/65A provides four transducer inputs and fourtemperature inputs. Software can configure each transducerinput to support 2-and 3-wire accelerometers, velocitysensors or proximity sensors.Each temperature inputsupports Type E, J, K, and T thermocouples, and 2-or 3-wireRTDS.
Outputs
The 1900/65A provides six relay outputs, four 4-20 mArecorder outputs, and a dedicated buffered output. The usercan use the 1900 Configuration software to configure therelay contacts to open or close according to the Ok, Alert andDanger statuses of any channel or combination of channels.and to provide data from any variable from any channel onany recorder output. The dedicated buffer output can providethe signal for each transducer input.

1900/65A-00-01-03-01-01
Product parameter
Transducer inputs
Users can configure Channels l through 4to accept input from acceleration,velocity or displacement transducers.
Transducer channel Types
Channel Types define the functionalityfor processing that will be applied to aninput signal and the kind of variables ormeasurement values that will be derivedfrom this input. Channel Types alsodefine the kind of sensor that must beused. Transducer Channel Types include:
Acceleration or ReciprocatingAcceleration
Velocity or Reciprocating VelocityRadial Vibration(shaft vibration)Thrust (shaft axial displacement)Position
speed
Application field
A Modpus Gateway option alows the monitorto provide static variables, statuses, event list,time and date information directly to anyModbus client, including Distributed ControlSystems (DCss),supervisory Control and DataAcquisition(SCADA)systems,ProgrammableLogic Controllers (PLCs),or System l software.The monitor uses aninternal counter and aModbus client/master time reference togenerate time and date information.Users canupgrade monitors without the ModbusGateway by ordering the 1900/01Communications Upgrade (see the OrderingInformation section).The 1900/65A supportsModbus communications via Ethernet and csoftware-configurable Rs232/485 serial port.
Configuration
The user defines monitor operation and theModbus Gateway register map by usingsoftware running on a laptop or PC to create aconfiguration file and download the file to themonitor through the built-in Ethernetconnection.The 1900/65A permanently storesconfiguration information in non-volatilememory, and can upload this information tothe PC for changes.
Display Module
The 1900/65A supports an optionaldisplay/keypad to view channel information ormake minor configuration changes. This allowsthe 1900/65A to operate as a stand-alonepackage.lf desired, the user can mount thedisplay up to 75 metres(250 feet) from theMonitor Module.