Description
Technical Specifications
| Product Model | **FBM232** |
| Manufacturer | FOXBORO |
| Product Type | Analog Input Module |
| Input Channels | 8 isolated channels |
| Signal Range | 4-20 mA / 0-10 VDC |
| Resolution | 16-bit |
| Accuracy | ±0.05% of span |
| Communication Protocol | Foundation Fieldbus H1 |
| Power Supply | 24 VDC ±10% |
| Operating Temperature | -40°C to +70°C |
| Certifications | SIL 2, ATEX Zone 2 |
| Housing Protection | IP67 |
Key Features and Advantages
The **FBM232** delivers exceptional signal integrity in critical process control applications. Its channel-to-channel isolation (1500 VAC) prevents ground loop interference, while the dual-range configurability allows seamless integration with both current and voltage field devices. Advanced diagnostics include wire-break detection and out-of-range alerts, enabling predictive maintenance strategies.
Engineered for hazardous areas, the module’s intrinsically safe design meets ATEX requirements without external barriers. The hot-swappable design permits module replacement during system operation, minimizing process downtime. Its Foundation Fieldbus H1 protocol ensures native compatibility with FOXBORO DCS systems while supporting multi-vendor interoperability.

FBM232-P0926GW
Application Areas
In chemical processing plants, the **FBM232** accurately monitors reactor pressure transmitters and flow meters for batch process optimization. Oil & gas platforms utilize its ruggedized design to collect tank level data in offshore environments. Power generation facilities rely on its SIL 2 certification for safety-critical boiler temperature monitoring, while water treatment plants leverage its high-resolution inputs for precise pH/ORP measurement loops.
Related Products
**FBM231**: 16-channel digital input module.
**FBM233**: Analog output counterpart with 4 channels.
**FBM207**: Communication gateway for legacy systems.
**P0926QX**: Redundant power supply for **FBM232** racks.
**IA Series**: Intrinsically safe transmitters optimized for **FBM232** integration.
Installation and Maintenance
Installation preparation: Verify field device compatibility with the **FBM232**’s signal ranges before wiring. Use shielded twisted-pair cables with proper glanding for IP67 integrity. Maintain minimum 30mm clearance between modules for adequate heat dissipation.
Maintenance recommendations: Perform annual calibration checks using the **FBM232**’s built-in test signals. Monitor communication load via the Foundation Fieldbus LAS tool to prevent network saturation. Replace terminal block springs every 5 years or 10,000 insertion cycles.
Product Assurance
FOXBORO’s **FBM232** undergoes 72-hour burn-in testing with full traceability to NIST standards. The 5-year warranty covers component failures, with expedited replacement available through global service centers. Comprehensive support includes configuration templates for DeltaV systems and on-site SIL verification services.