IRDH575B1W-435 | IRDH575B1-435 | Insulation monitoring device
Product Description
http://www.bender.ro/arhiva/fisa_tehnica/IRDH575_D00089_D_XXEN.pdf
Product description
The ISOMETER® of the IRDH575 series monitors the insulation resistance of unearthed
power supplies (IT systems). It is suitable for universal use in 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads, such as converters or thyristor-controlled DC drives. The IRDH575 in combination with EDS4… series insulation fault
locators and the appropriate measuring current transformers is designed to set up the respective equipment for insulation fault location.
Function insulation monitoring
When the insulation resistance between the system conductors and earth falls below the set response value, the alarm relays switch and the alarm LEDs light up. Two separately adjustable alarm relays (N/C or N/O operation) allow a distinction to be made between “prewarning” and “alarm”. The measured value is indicated on the LC display or an externally connectable measuring instrument. In this way any changes, for example when circuits are connected to the system, can be recognised easily. The fault message can be stored. The fault memory can be reset by pressing the internal or external reset button.
By pressing the test button, the function of the device as well as the connections to system and earth can be tested. Pressing the Info key provides additional information, such as the existing system leakage capacitance or device settings.

IRDH575B1W-435
Product parameter
• Response range 1 kΩ…10 MΩ
• Info button for the indication of various parameters and the system leakage capacitance
• Comprehensive self-monitoring function including system fault alarm relay
• Internal/external test and reset button
• Two separate alarm relays, N/C or N/O operation selectable
• Backlit plain text display 4 x 16 characters
• RS-485 interface
• Data memory, disconnection from supply and 0/4…20 mA current output
• Can be extended to an insulation fault location system for max.1080 circuits
• Adjustable locating current for insulation fault location
• Appropriate for EDS4… insulation fault location systems
• AMP measurement method
Application field