Product details:
Slot Covers
All unused slots in the case should be filled with blank I/O slot panels (Model 8105) to maintain proper air flow
All power modules are rated at 175 watts, which is sufficient to meet the system power requirements of all configurations in SR applications. Two Psus can be used in a chassis. The three models support different power supplies :120vac /DC(AC or DC), 230vac and 24vdc. The power module has a built-in diagnostic circuit to check for out-of-range voltage and/or overtemperature conditions. Indicator light emitting diode (led) in front
The interface of each power module provides the following module status:
-
PASS Green Input Power is OK
FAULT Red Power Module is not OK
ALARM Red Chassis Alarm Condition
TEMP Yellow Over-temperature Condition
BATT LOW Yellow Battery Low Condition
The power supply modules also contain the system alarm contacts. The chassis backplane
provides terminal strip interfaces for power and alarm connections. The alarm feature operates
independently for each power module.
On the main chassis, the alarm contacts on both power supply modules actuate on the following
states:
• System configuration does not match the control-program configuration
• A digital output module experiences a Load / Fuse error
• An AO module experiences a Load error
• A configured module is missing somewhere in the system
• A module is inserted in an unconfigured slot
• A fault is detected on a Main Processor or I/O module in the main chassis
• A fault is detected on an I/O module in an expansion chassis
• A main processor detects a system fault
• The inter-chassis I/O bus cables are incorrectly installed (i.e., cross connected)
The alarm contacts on at least one of the chassis power supplies will actuate when the following
power conditions exist:
• A power module fails
• Primary power to a power module is lost
• A power module has a low battery or over temperature condition
The alarm contacts on both power modules of an expansion chassis actuate when a fault is
detected on an I/O module.
Recommended model:
TRICONEX DO6603 Controller module |
Triconex SIS MP6004 Digital output module |
Triconex PM6301A Logic control module |
Triconex SIS AI6700 Distributed I/O module |
MOTOROLA MVME705B Analog output module |
FAUNC A06B-0590-B004#7008 servomotor |
GE VME-1064 Digital output module |
A06B-6077-H106 FANUC Control system power supply |
POWERBOX PU200-31C DO module |
TRICONEX 1600071-001 Network communication card |
MTL MTL5541 Safety grid |
Please contact Sunny sales@xiongbagk.cn for the best price.
➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com