Description
8310N2, 8311N2, AND 8312N2 POWER SUPPLY MODULESAll power supply modules are rated for 175 watts, which is sufficient to supply the power requirements of all configurations expected in SR applications. Two different power supply modules can be used in a single chassis. Three models are available to support different power sources: 120 VAC/DC (alternating or direct current), 230 VAC, and 24 VDC.
The 8310N2 power supply modules also contain the system alarm contacts. The chassis backplane provides terminal strip interfaces for power and alarm connections. The alarm feature operates independently for each power module. On the main chassis, the alarm contacts on both power supply modules actuate on the following states: • System configuration does not match the control-program configuration • A digital output module experiences a Load / Fuse error • An AO module experiences a Load error • A configured module is missing somewhere in the system • A module is inserted in an unconfigured slot • A fault is detected on a Main Processor or I/O module in the main chassis • A fault is detected on an I/O module in an expansion chassis • A main processor detects a system fault • The inter-chassis I/O bus cables are incorrectly installed (i.e., cross connected)
CONTACT US:
To order:Email below sales@xiongbagk,cn
【Manager: Sunny】
【Mobile: +86 18059884797】
【Whatsapp/ Wechat/Skype: +86 18059884797 】
Please contact Sunny sales@xiongbagk.cn for the best price.
➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com