BSFC-02C BSFC-12C charging controllers 

ACS880 frame size R8i inverter modules can be connected to the drive DC bus through a disconnector (or fuse-switch). This configuration requires a charging circuit to charge the DC capacitors of the modules in a controlled way. The DC voltage can be directly connected to the modules only after the capacitors are charged to a sufficient level. The BSFC is a unit that monitors the charging, and controls switch-on and switch-off of the DC voltage.
In addition to inverter units, the BSFC can be used with other units consisting of R8i modules, such as brake or DC/DC converter units. One BFSC unit can control the charging of up to 3 frame R8i modules.

Category:

Description

BSFC-02C BSFC-12C charging controllers

Product description

ACS880 frame size R8i inverter modules can be connected to the drive DC bus through a disconnector (or fuse-switch). This configuration requires a charging circuit to charge the DC capacitors of the modules in a controlled way. The DC voltage can be directly connected to the modules only after the capacitors are charged to a sufficient level. The BSFC is a unit that monitors the charging, and controls switch-on and switch-off of the DC voltage.
In addition to inverter units, the BSFC can be used with other units consisting of R8i modules, such as brake or DC/DC converter units. One BFSC unit can control the charging of up to 3 frame R8i modules.
The BSFC unit can be installed onto a standard mounting rail.

BSFC-02C

Product parameter

X4 Switch status monitoring (Q10 and Q11).
Power supply input for BSFC and operating voltage output for DC switch-disconnector locking
solenoid.
X5
V1…V6 Fiber optic links to inverters 1, 2 and 3.
Enable switches for charging circuit monitoring (inverters 1, 2 and 3).
Note: The BSFC unit does not allow the closing of the DC switch-disconnector unless monitoring
is enabled for at least one inverter module.
S1…S3
STAT Inverter charging status LEDs (3 pcs).
1…3
UDC 1…3 Inverter “ready for start” LEDs (3 pcs).
PWR BSFC power on LED

Application field

User turns charging switch [Q10] to position 1 (ON).
• Charging of the inverter capacitors starts through the charging resistors [R10]:
• Auxiliary contact 1-2 of charging switch [Q10] opens.
• BSFC prevents the starting of inverters and the closing of DC switch-disconnector [Q11].
• BSFC monitors inverter UDC signals through fiber optic link(s) INV1…INV3.
• INV STAT and PWR LEDs are on.
• When the charging is complete (inverter DC voltage over 80% of nominal):
• BSFC receives a UDC signal from the inverter(s).
• BSFC connects operating voltage to the solenoid of DC switch-disconnector [Q11]. The solenoid releases the locking mechanism, allowing operation of the handle.
• INV UDC and PWR LEDs are on.
• The Charging OK light [P11] on the cabinet door is on, indicating that the operation of the DC switch-disconnector [Q11] is allowed.
2. User turns DC switch-disconnector [Q11] to position 1 (ON).
• Main contacts 1-2…7-8 of DC switch-disconnector [Q11] connect inverter(s) to DC power supply.
• Auxiliary contact 13-14 of DC switch-disconnector [Q11] closes.
• Auxiliary contact 21-22 of DC switch-disconnector [Q11] opens, de-energizing the solenoid. The Charging OK light [P11] on the cabinet door goes off.
• INV UDC and PWR LEDs are on.
3. User turns charging switch [Q10] to position 0 (OFF).
• BSFC receives a “main switch ON, charging switch OFF” signal through terminal AUX2.
• BSFC sends an enable signal to inverter through the fiber optic link.
• INV UDC and PWR LEDs are on.