LD800HSE 3BDH000320R0101 FOUNDATION Fieldbus Linking Device LD 800HSE

The AO895 Analog Output Module has 8 channels. The module includes Intrinsic Safety protection

components and HART interface on each channel for connection to process equipment in

hazardous areas without the need for additional external devices.

Each channel can drive up to 20 mA loop current into a field load such as an Ex certified

current-to-pressure converter and is limited to 22 mA in overload conditions. All eight channels

are isolated from the ModuleBus and power supply in one group. Power to the output

stages is converted from the 24 V on the power supply connections.

Category:

Description

LD800HSE 3BDH000320R0101 FOUNDATION Fieldbus Linking Device LD 800HSE

LD 800HSE enables the access to field devices connected to the FOUNDATION Fieldbus (FF) from supervisory and

control systems as well as management consoles. The device is qualified for redundant use, where the corresponding

H1-ports of two Linking Devices are connected to one H1 link. A separate redundancy link between

primary and secondary Linking Devices ensures reliable failover and monitoring of redundancy.

Two different versions are available, one for safe areas and one for hazardous areas.

Are you looking for support or purchase information?

Services
  • Provides link between the FF’s High Speed Ethernet (HSE) protocol and up to four H1 links
  • Transparent configuration of connected H1 devices from host system
  • Allows access to blocks in H1 devices (Client/Server)
  • Four Independent H1 Link Masters (LAS)
  • Publish/Subscribe (H1) (with up to 4 sub-cycles)
  • Republishing of data from one H1 link into another or from H1 to HSE
  • Firmware update via download

LD800HSE

FOUNDATION Fieldbus (FF) is a fieldbus protocol based on international
standards and designed for applications in the manufacturing industry, process
automation and buildings automation. The guidelines for this fieldbus standard are
published by the Fieldbus Foundation.
FF defines two communication profiles, H1 and HSE. The H1 profile, with a
transmission rate of 31.25 kbit/s, is preferably used for direct communication
between field devices in one link (H1 link). The HSE profile, which is based on
standard Ethernet and typically features a transmission rate of 100 Mbit/s, serves
first and foremost as a powerful backbone for the connection between H1 links. The
first devices that are already available on the market and support the HSE profile are
FF linking devices. They serve as a gateway between the field devices on the H1
links and the HSE subnet.

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “LD800HSE 3BDH000320R0101 FOUNDATION Fieldbus Linking Device LD 800HSE”

Your email address will not be published. Required fields are marked *

Post comment