SR469-P5-HI-A20-E  SR 469 Motor Management Relay

The SR469-P5-HI-A20-E is from GE Multilin and is part of the SR 469 Motor Management Relay line.

This unit is designed with 5 amp phase CT secondaries.  Designed for use with medium-voltage motors, SR 469 relays offer integrated management and protection.

The SR469-P5-HI-A20-E offers 70-265 VAC, 90-300 VDC control power.   This unit has an enhanced front panel.

Category:

Description

SR469-P5-HI-A20-E  SR 469 Motor Management Relay

The SR469-P5-HI-A20-E is from GE Multilin and is part of the SR 469 Motor Management Relay line.

This unit is designed with 5 amp phase CT secondaries.  Designed for use with medium-voltage motors, SR 469 relays offer integrated management and protection.

The SR469-P5-HI-A20-E offers 70-265 VAC, 90-300 VDC control power.   This unit has an enhanced front panel.

However, if you need a unit that can be used within a harsh environment, please refer to our listing for the

SR469-P5-HI-A20-E-H, which is like this unit in every way with the exception of an additional harsh environment conformal coating.

The SR469-P5-HI-A20-E has a well-designed front panel that offers ease of use.  The panel includes an

RS-232 program port interface with a 9600 baud rate, programmable up to 19,200 baud.  This panel has a

draw-out handle that can be sealed to prevent any sort of unauthorized removal.  The front panel has a large

LCD display with forty character capabilities.   Users can see diagnostic messages like trips or alarms locally

through this display.   Additionally, the panel has motor and output status indicators, unit indicators, a numeric

keypad, control and programming keys, including a reset, escape, and menu button, and value keys that will allow users to change setpoint values.

SR469-P5-HI-A20-E

What should be done about unbalanced bias of thermal capacity’s and bias K factors with a GE SR469-P5-HI-A20-E Motor Management Relay?
With a GE SR469-P5-HI-A20-E Motor Management Relay having an unbalaned bias of thermal capacity’s, it
should be enabled to the thermal capacity usage so the heating effect of the unbalanced bias currents are added
to the thermal capacity. With an unbalanced bias K factor the value is calculated by the contribution of the negative
current that flows in the rotor due to the unbalance of the K factor. There is a formula that is based on data stats
that are empirical to the letter “K”, and it is equal to 230 divided by the per unit locked rotor current that is all
squared. The locked rotor amps = 631 percent FLA or 6.31 multiplied by the FLA.
What is the hot and cold curve ratio for this Relay SR469-P5-HI-A20-E?
By using the data sheets from the SR469-P5-HI-A20-E Relay, the safe stall hot and cold time curve ratio is set as
16/18 which is equal to 0.89. The hot and cold curve ratio is simply calculated by dividing the hot safe stall time by
the cold safe stall time, the motor thermal limits curve can be used as well.

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “SR469-P5-HI-A20-E  SR 469 Motor Management Relay”

Your email address will not be published. Required fields are marked *

Post comment