F8652X 984865265 F 8652X: Central module

For the serial interface only the bus station no. 1-31 can be set.Within an Ethernet network

the bus station no. can be set from 1 to 99. Therefore the switchesS1-6/7 must be set in addition

to the switches S1-1/2/3/4/5.The number of the communication partners within a network is still limited to 64.

This enhanced setting of the bus station no.

Category:

Description

TRICONEX F8652X 984865265 F 8652X: Central module

For the serial interface only the bus station no. 1-31 can be set.Within an Ethernet network

the bus station no. can be set from 1 to 99. Therefore the switchesS1-6/7 must be set in addition

to the switches S1-1/2/3/4/5.The number of the communication partners within a network is still limited to 64.

This enhanced setting of the bus station no. is only possible from operating system BS41g/51qV7.0-8 (05.31)of the central module.
Applications with the communication module F 8627X:connection of the central module to a PADT (ELOP II TCP)

connection to other communication partners within an Ethemet network (safeethernet.Modbus TCP)The communication

runs from the central module via the backplane bus to the communicationmodule F 8627X and from the

Ethemet ports of the F 8627X into the Ethernet network and viceversa.
Special features of the central module:
Self-education: from operating system BS41g/51g V7.0-8 (05.31)ELOP ll TCP: from operating system Bs41g/51q V7.0-8 (05.31)
Further informations about the bus station no., ELOP ll TCP, loading of operating systems andapplication programs

(self-education) et al. corresponding to the central module you will find inthe data sheet of the F8627X as well

as the operating system manual of H41q/H51g and thesafety manual of H41g/H51q.

F8652X-984865265

Diagnostic display of the central module
Four digit alphanumerical display,
two LEDs for the general display of errors (CPU for the central modules, l0 for the testableinput/output modules),two

toggle switches to request detailed error information,push-button ACK resets the error indication;in failure stop ACK

behaves like restarting the system.For further information on the diagnostic display and lists of error codes, refer to the

documen.tation “Functions of the operational system BS 41g51g” (also on ELOP II CD).
Notes for start-up and maintenance
-Lifetime of the buffer battery (without voltage feeding):
1000 days at T= 25 °C
200 days at TA = 60 °C
It is recommended to change the buffer battery (CPU in operation) at the latest after 6years, or with display BATl within three

months(Lithium battery,e.g.type CR 2477N, HIMA part no.44 0000018)Check the bus station no. and transmission

rate at switch S1 for correct settingsThe F 8652X can be used to replace the previous moduls: F 8652,F 8652A and F 8652E!

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “F8652X 984865265 F 8652X: Central module”

Your email address will not be published. Required fields are marked *

Post comment