These modules must be used only with Experion PKS R410 and later. These modules will not work as expected
with earlier releases of Experion PKS. Using these with Experion releases prior to R410 by downgrading the
firmware may render the module faulty and may not be possible to recover.

Category:

Description

CC-GAIX11   Supported Series C I/O modules

These modules must be used only with Experion PKS R410 and later. These modules will not work as expected
with earlier releases of Experion PKS. Using these with Experion releases prior to R410 by downgrading the
firmware may render the module faulty and may not be possible to recover.
NOTES:
1. There are two models of High Level Analog Input such as, CU-PAIX01 and CU-PAIN01. The Module
Hardware and the corresponding IOTAs are different and CU-PAIN01 is a new model. From the perspective
of configuration and implementation, both High Level Analog Input models use the same IOM Block such
as, AI-HL. It must be noted that the two models utilize the same configuration; online migration is not
possible as mixed redundant pair is not possible. There are two models of Analog Output such as, CUPAOX01

and CU-PAON01. Hence, similarly configuration, implementation, and interoperability constraints
apply and CU-PAON01 is the new model.
2. Two new models of AI-HART (CC-PAIH02) and AI-HL (CC-PAIX02) modules are introduced to replace
the older models of the AI-HART (CC-PAIH01) and AI-HL (CC-PAIX01) modules. The new models
support both single-ended and differential inputs.

CC-GAIX21

With R410, a new model of HART Analog Input CC-PAIH51 is introduced. The HART Analog Input CCPAIH51 and

Cx-PAIH01 use the same IOM block, that is, AI-HART. The configuration and implementation
mentioned in note 1 applies to the HART Analog Input module.
4. With R410, a new model of HART Analog Output CC-PAOH51 is introduced. The HART Analog Output
CC-PAOH51 and Cx-PAOH01 use the same IOM block, that is., AO-HART. The configuration and
implementation mentioned in note 1 applies to the HART Analog Output module.
5. With R410, a new model of Digital Input 24V DC CC-PDIL51 is introduced. The Digital Input 24V DC CCPDIL51 and

Cx-PDIL01 use the same IOM block, that is, DI-24. The configuration and implementation
mentioned in note 1 applies to the Digital Input 24V module.
6. With R410, a new model of Digital Output 24V DC CC-PDOD51 is introduced. The Digital Output 24V DC
CC-PDOD51 and Cx-PDOB01 use the same IOM block, that is, DO-24B. . The configuration and
implementation mentioned in note 1 applies to the Digital Output 24V module.
7. Starting with R430, a new model of Low Level Analog Input Mux CC-PAIM51 is introduced.
8. The UIO (CC-PUIO01) has 32 configurable input or output channels. Each channel can be configured as
one of the following:
• Analog Input (0-20mA or 4-20mA active)
• Analog Output (4-20mA active)
• Digital Input (with or without line monitoring)
• Digital Output (with or without line monitoring)

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “CC-GAIX11   Supported Series C I/O modules”

Your email address will not be published. Required fields are marked *

Post comment