9907-1200   Current-to-Pressure Converter

The CPC-II (current to pressure converter, generation II) is an electrohydraulic pressure-regulating

valve control designed for use in positioning single-acting steam turbine valve servos. This CPC’s superb

accuracy and resolution make it ideal for steam turbine valve control and related turbine speed and load

control. The CPC accepts a 4–20 mA pressure demand signal and accurately controls oil pressure to

precisely position single-acting steam turbine governor-valves. Precise and stable steam valve control directly relates to improved steam turbine

speed and load control and reduced system mechanical wear.

Category:

Description

9907-1200   Current-to-Pressure Converter

The CPC-II (current to pressure converter, generation II) is an electrohydraulic pressure-regulating

valve control designed for use in positioning single-acting steam turbine valve servos. This CPC’s superb

accuracy and resolution make it ideal for steam turbine valve control and related turbine speed and load

control. The CPC accepts a 4–20 mA pressure demand signal and accurately controls oil pressure to

precisely position single-acting steam turbine governor-valves. Precise and stable steam valve control directly relates to improved steam turbine

speed and load control and reduced system mechanical wear.

The CPC’s redundancy features make it ideal for critical steam turbine applications,

where turbine up-time and availability are essential. This converter can be configured to

accept redundant pressure demand inputs, from one or two (redundant) controllers, and

vote the input to follow. Alternatively the CPC can be configured to accept signals from

both its internal oil pressure sensor and an external (redundant) oil pressure sensor, and

use the voted healthy signal.

The CPC’s robust design (strong actuator, corrosion-resistant material, single moving

rotary valve, and self-cleaning port design) makes it ideal for challenging applications

where dirty or contaminated oil may be present.

Optionally two controllers can be connected to a single CPC in a redundant Master/Slave

fashion to allow the turbine to continue to operate if either turbine control fails, or on-line

changes are desired. Designed for use in applications requiring full redundancy,

optionally two CPCs can be applied in a dual-redundant fashion, simplifying the entire

system and control wiring.

The CPC is an electrohydraulic pressure-regulating valve control that utilizes a very

accurate internal pressure sensor and PID controller to precisely control steam turbine

valves. The CPC consists of a valve-actuator assembly, pressure sensor, and electronic

driver module. The unit’s driver module accepts one (or two) 4–20 mA pressure setpoints

and compares these setpoints to the sensed oil pressure, to accurately control turbine

valve oil pressure.

The CPC controls oil pressure by porting supply-oil to its control-oil output port (turbine

valve control oil) or back to the system supply tank. This converter’s special PID

architecture allows it to perform very stable pressure control during normal conditions,

and respond in milliseconds to desired valve step changes during system or plant

transients. As a means of protecting the turbine, an internal valve-return-spring forces the

CPC to a failsafe position (port oil to drain) and safely close turbine control valves upon

any internal unit failure (electrical input power failure, pressure sensor failure, processor

failure, etc.).

Please contact Sunny sales@xiongbagk.cn for the best price.

➱ sales manager: Sunny
➱ email mailto: sales@xiongbagk.cn
➱ Skype/WeChat: 18059884797
➱ phone/Whatsapp: + 86 18059884797
➱ QQ: 3095989363
➱ Website:www.sauldcs.com

Reviews

There are no reviews yet.

Be the first to review “9907-1200   Current-to-Pressure Converter”

Your email address will not be published. Required fields are marked *

Post comment